Automatic stabiliser bypass via an ATS: how to stop wasting energy
A voltage stabiliser works around the clock, even when the grid has exactly 230 V and there is nothing to correct. And every kilowatt-hour that passes through it is partly turned into heat. An acquaintance of ours put together simple automation: a voltage relay and an ATS route the house past the stabiliser by themselves when the voltage is normal, and switch on stabilisation only when it is really needed. Here we look at this scheme: how it works, which devices are suitable, how much it really saves and where mistakes can be made.
Who needs this
- You have a whole-house stabiliser, and the voltage is normal most of the day and only sags in the evening or after scheduled outages.
- The stabiliser is installed in front of the inverter input so that the battery + inverter kit does not drain the battery when the grid has 180 V in the evening.
- A lot of energy passes through the stabiliser: an electric stove, an electric grill, a water heater, a washing machine, heaters.
- You want the house not to be left without power if the stabiliser fails or has to be removed for repair.
Why a stabiliser uses energy even when the voltage is normal
A household relay, triac or thyristor stabiliser is built around an autotransformer. Its losses consist of two parts:
- No-load losses. The transformer, control board, display and fan consume energy even when there is no load. Manufacturers state this in their datasheets: the Volter SNPTO-9 “10–20 W at no load”, the Volter PTTM “no more than 20 watts”, Ferumina QUEST, ACTION and STATUS series “20–25 W”, the SNTO by the manufacturer Strum “10–20 W”. Around the clock that is 7–18 kWh a month.
- Losses under load. The current flowing through the windings and power switches heats them up. That is why datasheets state the efficiency: for the thyristor Volter 9 PTS it is 98%, for the Garant and Oberig stabilisers “over 95%”. So 2 to 5% of the energy passing through the stabiliser turns into heat.
Measurements confirm the same. In a study published in the journal Measurement: Energy in 2026 (Garabitos-Lara et al., DOI 10.1016/j.meaene.2025.100080), a 1580 VA household autotransformer had an efficiency of 98.0% at rated load, and its daily efficiency on real household consumption profiles stayed at 96.5–96.8%. That is, about 3.2–3.5% of the energy per day went into heat. This is a different device from an 8 kW stabiliser, but the principle is the same.
When the grid voltage is 225–235 V, the stabiliser effectively does nothing, yet these percentages are still lost. Hence the idea: during such hours, route the current past it.
How the automatic bypass works
Many stabilisers have their own “Stabilisation / Transit” switch, but it is manual, and switching it under load is forbidden. For example, the Volter PTTM datasheet states plainly: “It is FORBIDDEN to change the position of the ‘Stabilisation – Transit’ switch under load.” So instead, external automation made up of three devices is installed:
- An ATS (automatic transfer switch) with two inputs. Input I is fed directly from the grid, input II from the stabiliser output. The ATS gives priority to input I and switches to input II only when the voltage on input I disappears.
- A voltage relay through which input I is fed. While the voltage is within the settings, the relay contact is closed. As soon as the voltage goes outside the limits, the relay opens the contact, the ATS “thinks” input I has gone and switches the house to the stabiliser.
- The stabiliser, which is switched on all the time and waiting. Its own switch stays in the “Stabilisation” position.

When the voltage returns to normal, the relay waits for the set delay and closes the contact again. The ATS sees voltage on input I and returns the house to the bypass. If the voltage goes outside the operating range of the stabiliser itself, it switches off its output on its own, and the battery + inverter kit, if there is one, switches to the battery.
Wiring diagram

After the main breaker, the grid splits into two branches. The first goes through the voltage relay to input I of the ATS (the bypass). The second goes through the stabiliser breaker to the stabiliser, and its output goes to input II of the ATS. The ATS output feeds the house distribution board or the inverter input.
In our acquaintance’s setup the relay does not break the power phase, but only the phase on the control terminal of input I of the ATS. He has a two-pole TOMZN TOQ5 ATS: next to each input there are small control terminals, AR and AN for input I, BR and BN for input II, plus NC, C, NO signal contacts. The phase reaches the AR terminal through the voltage relay contact. The relay opens it, the ATS considers input I absent and switches to the stabiliser, even though the power phase on input I remains. Only a weak current flows through the relay, and its contacts hardly wear.
If your ATS has no such terminals, the relay is placed in the power phase of input I, and then its rated current must be no lower than the main breaker. And if the terminals are there, before connecting check the purpose of each one against the diagram on the housing or in the manual of your specific model.
What it looks like in real life

On the left is an 8 kW thyristor stabiliser, in the middle a small automation board: the ATS at the top, below it the breakers and a voltage relay with a display. On the right is a hybrid inverter with two outputs, fed by the ATS output. All the bypass automation fitted into one small enclosure.
Which devices are suitable
| Device | Example model | What matters (per datasheet) |
|---|---|---|
| Voltage relay | ZUBR D63t (DS Electronics) | 63 A, up to 80 A for 10 min. Upper limit 220–280 V, lower 120–210 V (factory settings 242 and 198 V). Switch-on delay 3–600 s. Power consumption no more than 1.5 kWh a month. 60-month warranty. |
| ATS | TOMZN TOQ5, 2 poles (as in our acquaintance’s setup) | Separate input control terminals (AR, AN and BR, BN) and NC, C, NO signal contacts. A Manual / Auto switch. In automatic mode it returns to input I as soon as voltage appears on it. |
| ATS | CHINT NXZBN-63, 2 poles | 10–63 A, 230 V, “auto-switching with auto-return” mode. Its own input I thresholds are not adjustable: 184 and 276 V, so without a voltage relay the ATS would switch too late. Mechanical endurance 10,000 cycles, electrical 3,000. |
| Stabiliser | thyristor type, for example Volter 9 PTS or 9 PTSSh | Efficiency 98%, switch-on delay 4.5–7.5 s. Input range 170–265 V (PTS) or 145–285 V (PTSSh). Power with a margin, as we explained in the article on choosing a stabiliser. |
| Breakers | QF1, QF2 on a DIN rail | Rating no higher than the current of the relay, ATS and stabiliser. A separate breaker in front of the stabiliser lets you remove it for repair while the house is powered through the bypass. |
The models are given as examples, with specifications from the manufacturers’ documentation. Others will do too, if their parameters are no worse. Before buying an ATS, check in its manual exactly how it monitors the inputs and whether it can return to input I automatically.
How to set up the voltage relay
| Parameter | Where to start | Why |
|---|---|---|
| Lower limit | 198–207 V | Below this voltage stabilisation switches on. 207 V is the lower limit of the 230 V −10% standard under DSTU EN 50160. |
| Upper limit | 242–250 V | Do not set it above 253 V (230 V +10%): above that the stabiliser should lower the voltage. |
| Return delay | 60–180 s | If the voltage “wanders” around the threshold, the ATS will not click every minute. The CHINT NXZBN has an electrical endurance of 3,000 switchings, and it is better to save them. |
Look at what voltage you get in the morning, during the day and in the evening: many relays, including ZUBR, show it on the display and keep a log of trips. If in the evenings the voltage stays at 200–205 V, the lower limit should be raised so that the stabiliser switches on earlier.
How much it really saves
The savings equal the stabiliser’s losses during the hours when the house runs through the bypass. It is easy to calculate: the energy passing through the stabiliser in a month, multiplied by 2–5%. If the voltage is normal not all the time but, say, 80% of the time, multiply the result by a further 0.8.

| Household consumption | Losses under load (2–5%) | In UAH at the tariff of 4.32 UAH |
|---|---|---|
| 300 kWh a month (apartment) | 6–15 kWh | 26–65 UAH a month |
| 600 kWh a month | 12–30 kWh | 52–130 UAH a month |
| 1000 kWh a month (house with an electric grill, water heater) | 20–50 kWh | 86–216 UAH a month |
| 1500 kWh a month | 30–75 kWh | 130–324 UAH a month |
Our acquaintance estimated the savings at 30–50 kWh a month. This matches the calculation for a house where about 1000 kWh a month passes through the stabiliser. The tariff of 4.32 UAH per kWh applies to households as of November 2026.
No-load losses (grey bars, 7–18 kWh a month) do not go away in this scheme: the stabiliser is switched on and waiting. They can also be saved only with the option of switching the stabiliser off completely, described below.
Measurement will show the savings most accurately. Put a DIN-rail meter on the input and output of the stabiliser and look at the difference over a week in normal operation. Some stabilisers, for example Ferumina, count the energy consumed by the load per day themselves.
What else this scheme gives besides savings
- Less heat and noise. Most of the time the stabiliser is unloaded, the fan spins less often and the power switches do not heat up.
- A fallback in case of failure. If the stabiliser shuts down or breaks, at normal voltage the house will stay on the grid through input I.
- Extra protection. The voltage relay on input I will not let voltage outside the limits into the house, even if the stabiliser is switched off.
- Maintenance without a power cut. The stabiliser can be switched off with breaker QF2 and removed, while the house runs through the bypass.
Full scheme with an inverter and a manual bypass
In our acquaintance’s setup, the ATS output feeds the input of a hybrid inverter with two outputs. Lighting and sockets are connected to the main output, and the washing machine and electric grill to the second. The inverter switches off the second output first when the battery runs low, so the main group runs longer. This function is available, for example, on the GSIKE 11 kW 48 V (second output up to 5.5 kW), the POWLAND SMS-12KW 12 kW and the POWLAND SMS-6.5KP 6.5 kW.

Between the inverter and the groups there is a four-pole I–0–II manual changeover switch (three poles are used: the main output phase, the second output phase and the neutral). In position I the house is powered by the inverter. In position II both groups get the grid directly through the stabiliser bypass, while the inverter output is fully disconnected, so it can be switched off, updated or removed for repair. The switch also breaks the neutral, so the inverter output will never be connected to the grid.
Why have a stabiliser in front of the inverter? When the grid is present, a hybrid inverter passes its voltage through to the output practically unchanged. If in the evening the grid has 185 V and the inverter is set to accept 90 to 280 V (“appliances” mode), your appliances will get the same 185 V. The stabiliser fixes this, and the bypass removes its losses when it is not needed. More on this in the article on the hybrid inverter.
The “maximum” option: switching the stabiliser off completely
To also save the 7–18 kWh of no-load losses, the stabiliser can be de-energised while the house runs through the bypass. To do this, the stabiliser is fed through a contactor controlled by the same voltage relay via an intermediate relay with a normally closed contact. Voltage normal: the contactor is open, the stabiliser is off. Voltage outside the limits: the contactor switches the stabiliser on, after 4.5–7.5 s (the Volter delay) voltage appears at its output, and the ATS switches to input II.
The downside is that for these few seconds the house is left without the grid. If a battery + inverter kit is installed after the ATS, nobody will notice: the inverter will switch to the battery. Without an inverter, the fridge, boiler and pump will get a short interruption. In addition, each time it is switched on the stabiliser’s transformer causes an inrush current, so the rating and characteristic of breaker QF2 are selected by an electrician. We recommend this option only for systems with an inverter.
Important: safety
Never connect the grid and the stabiliser output with two separate breakers or contactors without a mechanical interlock. A stabiliser is an autotransformer: in boost mode such an overlap short-circuits part of the winding. Switching is done only by an ATS or an I–0–II switch with a mechanical interlock. Do not open the stabiliser or disable its built-in switch from the inside: this may void its warranty, and an external ATS does the same without interfering. Use a two-pole ATS, earth the stabiliser housing, and label the input I terminals: when the relay is open, they may remain live. Work in the distribution board is done by a qualified electrician.
Typical mistakes
- A low-current relay in the power circuit. A 25 or 32 A relay under a 40–50 A house load will overheat. The relay rating must be no lower than the main breaker.
- Zero return delay. The voltage fluctuates around the threshold, the ATS clicks dozens of times a day and quickly uses up its service life.
- An ATS without auto-return. If the ATS is set not to return to input I, the house will simply stay on the stabiliser, and there will be no savings. You need the “auto-switching with auto-return” mode.
- Thresholds wider than the standard. An upper limit of 270 V means that in bypass mode your appliances will get elevated voltage.
- Switching the manual inverter bypass without a pause at zero. The inverter and the grid must not be connected even for an instant.
In short: 8 tips
- A stabiliser is needed only when the voltage goes outside the standard. The rest of the time, route the house past it through an ATS.
- Feed ATS input I from the grid through a voltage relay, and input II from the stabiliser output.
- Leave the stabiliser’s own switch in the “Stabilisation” position and do not switch it under load.
- Start the relay thresholds at 198–207 V and 242–250 V, with a return delay of 60–180 s.
- The relay rating in the power circuit must be no lower than the main breaker. It is better if the ATS has separate input monitoring terminals.
- Savings of 2–5% of the energy passing through the stabiliser: for a 1000 kWh house that is 20–50 kWh a month.
- Check the savings with meters on the stabiliser input and output, not by eye.
- The stabiliser input and output are connected only by an ATS or a switch with a mechanical interlock. Installation is done by an electrician.
Frequently asked questions
Can I do without a voltage relay, since the ATS monitors the voltage itself?
On the CHINT NXZBN the input I thresholds are fixed: 184 and 276 V. Stabilisation would only switch on at 184 V, and until then your appliances would get, for example, 190 V. A voltage relay gives precise thresholds that you set yourself.
Will appliances notice the switching?
If there is an inverter after the ATS, no: during switching it powers the house from the battery. Without an inverter there will be a short pause while the ATS switches its contacts. For most appliances this is no problem, but a boiler or fridge may restart.
Doesn’t frequent switching wear out the stabiliser?
In the basic scheme the stabiliser is not switched on and off: it is constantly energised, and it is the ATS that switches. The ATS’s service life is protected by the return delay in the relay.
What if my voltage is always low?
Then the house will be on the stabiliser almost all the time, and the bypass will give little. The scheme is most useful where the voltage is normal for most of the day.
Expert opinion
An automatic stabiliser bypass is an inexpensive and sensible upgrade: three devices on a DIN rail eliminate pointless losses, reduce heating and provide a backup power path. The savings are not astronomical, for an ordinary house it is tens of kilowatt-hours a month, but they work every day and without your involvement. The scheme works best together with a battery + inverter kit: the inverter smooths out any switching, the battery covers outages, and the stabiliser switches on only when the grid is really bad.
Want to build this kind of automation or connect a stabiliser to a battery + inverter kit? We do turnkey installation in Dnipro. Call us: 093 293 93 93, 099 054 40 38. MinerTech engineers will advise on your specific task.